058 059
_
COMPREHENSIVE APPLICATION AND INSTALLATION MANUAL
LG Electronics
Installation check listConguration
System Design ApplicationsIntroduction
1.1 Piping installation
 
Items to check
Are pipings correctly connected?  
(Water piping, refrigerant piping)
Result
Purpose Check piping connection
Applicants AWHP SPLIT
Check in/outow of water piping connections
Check connections of refrigerant piping and gas/liquid piping 
Liquid-Refrigerant
(9.52 mm)
Gas - Refrigerant(15.88 mm)
[Tightening]
In-Water (PT) 
1)
Out-Water
(PT 1)
[Supporter]
1.2 Leakage test
 
Items to check
Was the standard airtight test run to check if there is any leakage from 
pipings and the product?  
(For R410A: 24-hour test with nitrogen pressure of 38 kg)
Result
Purpose Check for leakage on pipings
Applicants AWHP SPLIT
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with 
charge hoses.
Charge hose
Outdoor unit
Manifold valve
Lo Hi
Pressure 
gauge
Nitrogen gas
cylinder(in vertical
standing position)
A  Nitrogen gas
B  Manifold gauge
C  Low pressure cover
D  High pressure cover
E  Liquid pipe
F  Gas pipe
G  Service port
Indoor unit
Be sure to use a manifold valve for leakage test.
If it is not available, use a stop valve for this purpose.  
The "Hi" knob of the manifold valve must always be kept close.
•  Pressurize the system to no more than 3.0 Mpa with dry nitrogen gas and close the cylinder valve when 
the gauge reading reaches 3.0 Mpa Next, test for leaks with liquid soap.
 
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose 
connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the 
hose fromthe cylinder.