Liebert PW017 - 5.1.2 Water Supply-line Requirements for Optional Humidifier

Liebert PW017
153 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Factory-installed CondensatePump in UpflowUnits
NOTE: Condensate pumps are factory-installed on upflow units. They are shipped separately to be
field-installed on downflow units.
If your upflow unit requires a condensate pump, the pump is factory-installed inside the unit and a 1/2-in.
copper condensate-discharge connection is provided on the unit.
208-V condensate pump rated for 5 GPM at 45 ft (18.9l/m at 13.7m) of total head pressure.
230-V condensate pump rated for 5 GPM at 48 ft (18.9l/m at 14.6 m) of total head pressure.
460-V condensate pump rated for 5 GPM at 40 ft (18.9l/m at 12.2m) of total head pressure.
460-Vcondensate pump is also used on 380-V and 575-V units.
Size discharge piping based on available condensate head.
Field-installed Condensate Pump for Downflow Units
NOTE: Condensate pumps are factory-installed on upflow units. They are shipped separately to be
field-installed on downflow units.
If your downflow unit requires a condensate pump, the pump is shipped separately to be field-installed
alongside the unit or beneath the raised floor. If installing beneath a raised floor, a minimum 11in (280mm)
floor height is required.
A 3/4-in. NPT-Female drain connection is provided on the unit.
Drain is trapped internally. Do not trap external to unit.
208-V condensate pump rated for 5 GPM at 45 ft (18.9l/m at 13.7m) of total head pressure.
230-V condensate pump rated for 5 GPM at 48 ft (18.9l/m at 14.6 m) of total head pressure.
460-V condensate pump rated for 5 GPM at 40 ft (18.9l/m at 12.2m) of total head pressure.
460-Vcondensate pump is also used on 380-V and 575-V units.
Size the discharge piping based on available condensate head.
5.1.2 Water Supply-line Requirements for the Optional Humidifier
The unit may have one of the following optional humidifiers. Refer to the appropriate supply-line piping
requirements if a humidifier is included on your unit:
Infrared Humidifier:
1/4-in. supply line, maximum water pressure is 150 psi (1034kPa).
Size supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20psi(138kPa).
Do not supply de-ionized water to the humidifier.