Table 33:Modbus memory map: programming variables (Table 19)
Alarm: Fan
Configuration variable Address Valid data margin Default value
Value 114C 0 - 80 ºC 35
Enabled 114D 0 (OFF), 1 (ON) 0
Table 34:Modbus memory map: programming variables (Table 20)
Alarm: Voltage
Configuration variable Address Valid data margin Default value
Overvoltage value 114E-114F 0-99999 440
No Voltage Value 1150-1151 0-99999 360
Table 35:Modbus memory map: programming variables (Table 21)
No� of operations
Configuration variable Address Valid data margin Default value
No. of operations 1152-1153 1-99999 5000
Table 36:Modbus memory map: programming variables (Table 22)
Enabling alarms
Configuration variable Address Valid data margin Default value
Enable Alarm E01 1155
0 (OFF), 1 (ON)
1
Enable Alarm E02 1156 1
Enable Alarm E03 1157 1
Enable Alarm E04 1158 1
Enable Alarm E05 1159 0
Enable Alarm E06 115A 0
Enable Alarm E07 115B 0
Enable Alarm E08 115C 0
Enable Alarm E09 115D 0
Enable Alarm E10 115E 0
Enable Alarm E11 115F 0
Enable Alarm E12 1160 0
Enable Alarm E13 1161 0
Enable Alarm E14 1162 0
Enable Alarm E15 1163 0
Enable Alarm E16 1164 0
Enable Alarm E17 1165 0
67
Instruction Manual
Controller MASTER control VAR FAST

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lifasa MASTER control Var and is the answer not in the manual?

Lifasa MASTER control Var Specifications

General IconGeneral
BrandLifasa
ModelMASTER control Var
CategoryController
LanguageEnglish

Related product manuals