www.lifebreath.com
Page 19
SERVICE AND MAINTENANCE (2500 UNITS)
A dedicated maintenance program will prolong the life of the equipment and maintain its optimum
performance.
We recommend at least two (2) full inspections and cleanings per year under normal operating conditions and
more if circumstances warrant it (i.e., situations of heavy smoke may require servicing every one to two
months).
(1) Heat Exchanger Core
(2) Exhaust Hood c/w Bug Screen
(3) Motors (two)
(4) Roof Curb
(5) Supply Duct 24” x 16”
(6) Drain Pans (two)
(7) Exhaust Duct 24” x 16”
(8) 4” Filters (two)
(9) Supply Hood c/w Bug Screen
Services should include:
Cleaning of screens protecting outside
hoods.
Cleaning of core (see below).
Inspect filters and replace as necessary.
Wipe down drain pans and inside of cabinet
using a mild disinfectant.
Ensure condensate drain has free flow of
moisture.
Inspect operation of blowers and electric
panel.
Confirm operation.
Cleaning of Core:
To access core, remove service panels and slide core halfway out. Wash core protruding from cabinet with
water and/or a mild cleaning solution. Push core through to the other side of the cabinet and repeat the
procedure to the clean the other side of the core. In many cases, only a vacuuming of the core surface is
required.