Terminal A2
Function
Selection
0 : Main Frequency Command
1 : Frequency Gain
2 : Output Frequency Lower Limit
3 : Auxiliary Frequency Command
4 : Output Voltage Bias
5 : Acc./Dec. Time Gain (Decrease Only)
6 : DC Braking (DB) Current
7 : Stall Prevention Level During Run
8 : PID Feedback 9 : PID Target Value
10: Differential PID Feedback
11 : Overtorque/ Undertorque Detection
18: Communication Mode 1
19 : Communication Mode 2
20:V/F separation voltage
Default: 8
Range: 0 to 20
Sets the terminal A2 input gain as a
percentage when inputting 10V
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
Terminal A2
Input Voltage
Bias
Sets the terminal A2 input voltage bias as a
percentage when inputting 0V.
Default: 0.0%
Min.: -999.9 %
Max.: 999.9 %
Terminal A2 (4-
20mA) Loss
Action Selection
0 : Disabled
1 : Run According to P4-03 Setting and Display
ANL
2 : Disacceleration to 0Hz and Display ANL
3 : Drive Stop and Display ACE
Default: 0
Min.: 0
Max.: 3
Terminal A2
Input Filter Time
Sets the terminal A2 primary delay filter time,
which can eliminate the interference.
Default: 0.05 s
Min.: 0.00 s
Max.: 2.00 s
Analog Input
Terminal Enable/
Disable Selection
Enables the analog inputs when Multi-
Function Terminal Input E1-□□ = 41 (Multi-
Function Analog Input Selection).
0: Both Terminal A1 and A2 Disabled
1: Only Analog Input Terminal A1 Enabled
2: Only Analog Input Terminal A2 Enabled
3: Both Terminal A1 and A2 Enabled
Terminal A1 input lower limit (valid when A1