108
Parameter
Name
Description
Setting Range
Selection
Max.: 1
E5-09<4>
<7>
Average PWM
Signal Times
1 to 100 times
Default: 1
Min.: 1
Max.: 100
E5-10
<7>
PWM Signal
Cycle
1 to 999 ms
Default: 100 ms
Min.: 1 ms
Max.: 999 ms
E6: Optional Communication Card Settings
E6-06
Drive Station
Address
Sets the drive station address.
Default: 1
Range: 1 to 31
E6-07
RS-485
Communication
Baud Rate
Setting
Sets the baud rate for terminals SG(+) and
SG(-) of RS-485 communication.
0: 1200 bps (bit/sec)
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
Default: 3
Range: 0 to 8
E6-08
RS-485
Communication
Parity Selection
Selects the communication parity for
terminals SG(+) and SG(-) of RS-485
communication.
0: 8, N, 2 (Modbus RTU)
1: 8, N, 1 (Modbus RTU)
2: 8, E, 1 (Modbus RTU)
3: 8, O, 1 (Modbus RTU)
4: 8, N, 2 (Modbus ASCII)
5: 8, N, 1 (Modbus ASCII)
6: 8, E, 1 (Modbus ASCII)
7: 8, O, 1 (Modbus ASCII)
8: 7, N, 2 (Modbus ASCII)
9: 7, N, 1 (Modbus ASCII)
10: 7, E, 1 (Modbus ASCII)
11: 7, O, 1 (Modbus ASCII)
Default: 1
Range: 0 to 11
E6-09
Communication
Error Detection
Time
Determines the detection time to trigger the
communication error. (This function is
disabled when set to 0)
Default: 0.0 s
Range: 0.0 to 10.0 s
E6-10
Transmit Wait
Sets the wait time between sending and
Default: 5ms