value will be counted from 0.
Cumulative Drive
Operation Time
Displays the cumulative operation time for the drive.
The initial value is determined by o4-00. The maximum
number displayed is 60000, after which the value will be
counted from 0.
Displays the heatsink temperature.
Detects LED keypad working properly.
4 digits after kWh
(cumulative
power)
The output power of the inverter is displayed on the
monitor. It is displayed separately according to the high
and low positions. (Display example) The monitor at
12345678.9kWh is displayed as: U3-08: 678.9kWh U3-09:
12345MWh
5 digits after kWh
(cumulative
power)
The output power of the inverter is displayed on the
monitor. It is displayed separately according to the high
and low positions. (Display example) The monitor at
12345678.9kWh is displayed as: U3-08: 678.9kWh U3-09:
12345MWh
Displays the peak current value during operation
Peak Hold Output
Frequency
Displays the output frequency when the peak current
displayed in U3-10 occurred.
Motor Overload
Estimate (oL1)
Displays the value of the motor overload detection
accumulator. An oL1 will be triggered when reaching
100%.
Frequency
Command Source
Selection
Displays the source for the frequency command as XY-nn.
X: Command Used
1: Command 1
2: Command 2
Y-nn: Frequency Command Source
0-01: Keypad
1-01: Analog input (Terminal AI 1)
1-02: Analog input (Terminal AI 2)
2-02 to 2-16: Multi-step speed command
2-17: Jog frequency command
3-01: PID frequency command
4-01: Terminal UP/ DOWN
5-01: Modbus communication
6-01: Pulse train command
7-00 ~ 7-16 : Automatic operation command