51
◼ Do not connect power cable to output terminals of the drive. Failure to comply could cause
drive damage and a fire.
4.2.2.3 DC Reactor and Braking Resistor Terminal:
◼ The terminal is to connect a DC reactor so as to improve power factor. The drive is shipped
from the factory with a short-circuit jumper. Remove the jumper before connecting a DC
reactor.
◼ If the drive is used in a high-frequency or heavy duty application which requires frequent
braking or shorter deceleration time, install an optional braking resistor to increase the
braking torque.
◼ Please refer to the wiring diagram when installing braking options.
4.2.2.4 Ground Terminal
◼ Use grounding cables of dimensions regulated by electrical equipment standard. Shrink
wiring distance to prevent leakage current resulting unstable electrical potential at the
terminal distant from grounding terminal.
◼ Do not use share the same grounding cable with welding machines or any device requiring
large current. Failure to comply could cause drive or equipment malfunction.
◼ Do not wind the grounding cable when multiple drives are installed. Failure to comply could
cause drive or equipment malfunction.
◼ Ensure the neutral of the input side and drive terminal " “ are grounded according to
the local electrician regulations. 3WYE (e.g. TN and TT) system are suggested for the drive
primary side.
4.2.2.5 Jumper:
◼ EVO6800 complies with the European LVD standard EN 61800-5-1 (2007) reducing the touch
current to below 10mA DC under testing condition regulated by IEC 60990 (1999).