User-Defined
Parameter
Automatic Save
Saves the most recently edited parameters.
0: Do not save list of recently edited
parameters
1: Save list of recently edited parameters
b1: Operation Mode Selection
Frequency
Command
Selection 1
0
∶
Keypad
1
∶
Control Circuit Terminal (Analog Input)
2
∶
Terminal Up/Down
3
∶
Modbus Communication
4
∶
Pulse Train Input (Including PWM signal
input)
5
∶
Automatic operation
6: Expansion card
Default
∶
0
Min.: 0
Max.: 5
Remarks:
The maximum
number of models
above F3: 6
0
∶
Keypad
1
∶
Control Circuit Terminal (Sequence
Control Input)
2
∶
Modbus Communication
3: Expansion card
Default
∶
0
Min.: 0
Max.: 2
Remarks:
The Max. value for F3
and above is 3
Stopping
Method
Selection
0
∶
Ramp to Stop
1
∶
Coast to Stop
2
∶
DC Braking to Stop
3
∶
Coast to Stop with Timer
Default
∶
0
Min.: 0
Max.: 3
Reverse Rotation
Selection
0: Reverse Rotation Enabled
Drive accepts a run command of both
forward and reverse directions
1: Reverse Rotation disabled
Drive can accept only run command of
forward direction
Run Command
Action after
Switch
0: Ignore Active Run Command at the New
Source
If a Run command at the new source is active,
the drive will not start or the drive will stop
operation if it was running when switching
from the old source to the new source. The
drive can start only when the Run command
is removed and given again.
Default
∶
0
Min.: 0
Max.: 1