Speed search
deceleration
time
Sets the search speed in the deceleration
time (The maximum output frequency to the
minimum output frequency deceleration
time)
Default
∶
2.0s
Min.: 0.1s
Max.: 10.0s
Remarks:
Default setting of
40HP (included) or
above: 3.5 s
In order to reduce the speed of search output
current by the V / f curve calculated by
multiplying the voltage set value b3-05 by
adjusting the setting, the speed can be
suppressed search output current.
Default: 100%
Min.: 10 %
Max.: 100%
Remarks:
Default setting of
60HP (included) or
above: 80%
Timer Function
On-Delay Time
Sets the on-delay and off-delay time to switch
on/off the timer output.
Default
∶
0.1 s
Min.: 0.1 s
Max.: 3000.0 s
Timer Function
Off-Delay Time
Default
∶
0.1 s
Min.: 0.1 s
Max.: 3000.0 s
0
∶
PID Control Disabled
1
∶
PID Control Enabled (D Control for
Deviation Signal U4-01)
2
∶
PID Control Enabled (D Control for
Feedback Signal U4-05)
3
∶
PID Control Enabled (Frequency
Command
+
PID Output from D Controlled
Deviation)
4
∶
PID Control Enabled (Frequency
Command
+
PID Output from D Controlled
Feedback)
5 : PID Control Disabled
,
but b5-14/b5-15
(PID Sleep) and b5-29/b5-30(PID Wake-up)
Enabled
Default
∶
0
Min.: 0
Max.: 5
Proportional
Gain Setting (P)
Sets the P gain for PID input.
Default
∶
1.00
Min.: 0.00
Max.: 25.00