Drive accepts an active run command at
power up and runs the motor immediately.
Local/ Remote
switching Enable
during Operating
Default
∶
0
Min.: 0
Max.: 1
Zero Speed
Holding (DC
Braking) Start
Level
Sets the start frequency for Zero Speed
Holding (DC braking). Enabled when b1-02
(Stopping Method Selection) is set to 0 (Ramp
to Stop)
Default
∶
0.5Hz
Min.: 0.0 Hz
Max.: 400.0 Hz
Sets the DC braking current as a percentage of
the drive rated current
Default
∶
0%
Min.: 0%
Max.: 100%
Sets the DC braking time at start to stop a
coasting motor before restarting it or to apply
braking torque at start when high starting
torque is needed.
Disabled when set to 0.00.
Default
∶
0.00 s
Min.: 0.00 s
Max.: 99.99 s
Sets the DC braking time at stop to stop a
motor rotating with high inertia.
Disabled when set to 0.00.
Default
∶
0.00s
Min.: 0.00s
Max.: 99.99s
0
∶
Disabled
1
∶
Enabled and searched from the highest
frequency
2
∶
Enabled and searched from the
frequency command
3
∶
Retain
4
∶
Retain
Default: 0
Min.: 0
Max.: 2
Speed Search
Operating
Current
Sets the current level as a percentage of the
drive rated current below which Speed Search
is deactivated.
Default: 120%
Min.: 30 %
Max.: 140%
Sets the search speed in the output voltage
restoring to the time set v / f voltage curve
required
Default
∶
0.6s
Min.: 0.3s
Max.: 5.0s
Remarks:
Default setting of
60HP (included) or
above: 1.0 s