83
Parameter
Name
Description
Setting Range
Drive accepts an active run command at
power up and runs the motor immediately.
b1-12
Local/ Remote
switching Enable
during Operating
0
Disabled
1
Enabled
Default
0
Min.: 0
Max.: 1
b2: DC Braking
b2-00
Zero Speed
Holding (DC
Braking) Start
Level
Sets the start frequency for Zero Speed
Holding (DC braking). Enabled when b1-02
(Stopping Method Selection) is set to 0 (Ramp
to Stop)
Default
0.5Hz
Min.: 0.0 Hz
Max.: 400.0 Hz
b2-01
DC Braking
Current
Sets the DC braking current as a percentage of
the drive rated current
Default
0%
Min.: 0%
Max.: 100%
b2-02
DC Braking Time
at Start
Sets the DC braking time at start to stop a
coasting motor before restarting it or to apply
braking torque at start when high starting
torque is needed.
Disabled when set to 0.00.
Default
0.00 s
Min.: 0.00 s
Max.: 99.99 s
b2-03
DC Braking Time
at Stop
Sets the DC braking time at stop to stop a
motor rotating with high inertia.
Disabled when set to 0.00.
Default
0.00s
Min.: 0.00s
Max.: 99.99s
b3: Speed Search
b3-00
Speed Search
Setting
0
Disabled
1
Enabled and searched from the highest
frequency
2
Enabled and searched from the
frequency command
3
Retain
4
Retain
Default: 0
Min.: 0
Max.: 2
b3-01
Speed Search
Operating
Current
Sets the current level as a percentage of the
drive rated current below which Speed Search
is deactivated.
Default: 120%
Min.: 30 %
Max.: 140%
b3-02
Voltage Rocevery
Time
Sets the search speed in the output voltage
restoring to the time set v / f voltage curve
required
Default
0.6s
Min.: 0.3s
Max.: 5.0s
Remarks:
Default setting of
60HP (included) or
above: 1.0 s