without an alarm displayed)
7 : Multi-Function Output Only (detection
working when drive running or not)
PID Feedback
Low Detection
Level
Sets the PID feedback level used for
detection. When the PID feedback falls below
this level for longer than the time set to b5-
13, PID feedback loss will be detected.
Default
∶
0%
Min.: 0%
Max.: 100%
PID Feedback
Low Detection
Time
Sets the PID feedback time used for
detection. When the PID feedback falls below
the level set to b5-12 for longer than this
time, PID feedback loss will be detected.
Default
∶
1.0 s
Min.: 0.0 s
Max.: 25.5 s
Sets the PID level to trigger the drive to sleep.
Default
∶
0.0Hz
Min.: 0.0 Hz
Max.:<5>
Sets the delay time used to
activate/deactivate the PID Sleep function.
When this parameter is set to 0.0, PID Sleep
function will be stopped.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 25.5 s
PID Command
Acc./Dec. Time
Sets the PID command acceleration
/deceleration time used for PID target soft-
start function.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 20.0 s
0
∶
PID Target Disabled
1
∶
PID Target Enabled
Default
∶
0
Min.: 0
Max.: 1
Sets the PID target value as a percentage of
the maximum output frequency when b5-
17=1 and no other ananlog input sets the PID
Target.
Default
∶
0.00%
Min.: 0.00%
Max.: 100.00%
0
∶
0.01Hz
1
∶
0.01% (Maximum Frequency is 100%)
2
∶
r/min. (Number of Motor Poles must be
set)
3
∶
User Defined (Defined by b5-24 and b5-
25)
Default
∶
1
Min.: 0
Max.: 3
Sets the lower limit as a percentage of the
maximum output frequency set in d1-02 for
PID output.
Default
∶
0.0%
Min.: -100.0%
Max.: 100.0%