The higher PID Input value is, the higher PID
output value will be. Sets this parameter to
limit the PID input value.
Default
∶
1000.0%
Min.: 0.0%
Max.: 1000.0%
PID Feedback
High Detection
Level
Sets the level for PID feedback high detection
as a percentage of the maximum output
frequency.
PID feedback high will be detected when the
feedback exceeds the level set in b5-22 for
longer than the time set in b5-23.
Default
∶
100%
Min.: 0%
Max.: 100%
PID Feedback
High Detection
Time
Sets the time for PID feedback high detection.
PID feedback high will be detected when the
feedback exceeds the level set in b5-22 for
longer than the time set in b5-23.
Default
∶
1.0 s
Min.: 0.0 s
Max.: 25.5 s
Sets a value to display to U4-00 and U4-03
when the drive runs at the maximum output
frequency
Determined by b5-19
Min.: 1
Max.: 60000
PID Target
Display Digits
Sets the number of decimal places to display.
0
∶
No Decimal Places
1
∶
1 Decimal Place
2
∶
2 Decimal Places
3
∶
3 Decimal Places
Determined by b5-19
Min.: 0
Max.: 3
Frequency
Command
Display During
PID
0 : Displays frequency command after the PID
compensation.
1 : Displays frequency command before the
PID compensation.
Default
∶
0
Min.: 0
Max.: 1
Sets the direction when PID output value is
minus.
0 : Reverse is not allowed.
1 : Reverse is allowed.
Default
∶
1
Min.: 0
Max.: 1
PID
Disconnection
Output
Frequency
When a PID feedback disconnection alarm
occurs, the drive will run at the frequency set
to b5-28, and return to PID control when
disconnection alarm is reset.
Default: 30.0 Hz
Min.:0.0Hz
Max.: <5>
Sets the PID Wake-up level
Default:0.0 Hz
Min.:0.0 Hz
Max.:<5>
Sets the PID Wake-up delay time
Default: 0.0 s
Min.: 0.0 s
Max.: 25.5 s