93
Parameter
Name
Description
Setting Range
Command 15
To use speed commands for each multi-step
speed, set E1-□□ to 5, 6, 7 and 8 (multi-step
speed command 1, 2, 3, 4). Sets E1-□□ to 9 for
Jog frequency command.
The upper limit is determined by d1-02 and L2-
00.
In PM Closed-Loop Vector Control, o1-00 will
be automatically set to 1 with the unit set to %.
When L2-00 (Frequency Upper Limit) is
adjusted, the exceeded frequency in L1-00 to
L1-15 will be automatically set to the upper
limit determined in L2-00.
Min.: 0.00Hz
Max.: <5>
L1-15 <4>
Frequency
Command 16
Default: 50.00Hz
Min.: 0.00Hz
Max.: <5>
L1-16 <4>
Jog Frequency
Command
Sets the Jog frequency command.
Default: 6.00 Hz
Min.: 0.00Hz
Max.: <5>
L2: Frequency Upper/ Lower Limit
L2-00
Frequency
Command Upper
Limit
Sets the upper limit
Default: d1-02
Min.: 0.0 Hz
Max.: d1-02*110%
L2-01
Frequency
Command Lower
Limit
Sets the lower limit as a percentage of the
maximum output frequency
Default: 0.0Hz
Min.: 0.0
Max.: d1-02*110%
L3: Jump Frequency
L3-00
Jump Frequency
1
Sets the Jump frequency range to avoid
operation at the speed causing resonance in
the machinery.
Set L3-00 to L3-03 to 0.0 Hz to disable Jump
frequency.
When setting more than 1 Jump frequency,
follow the condition below.
L3-00 L3-01 L3-02
Default: 0.0 Hz
Min.: 0.0
Max.: L2-00
L3-01
Jump Frequency
2
L3-02
Jump Frequency
3
L3-03
Jump Frequency
Range
Sets the Jump frequency range to avoid.
Default: 1.00 Hz
Min.: 0.00 Hz
Max.: 20.0 Hz