Up/ Down
Frequency
Command Hold
Determines whether or not to save the
frequency command or the frequency bias
(Up/Down 2) value when the Stop command
is entered or the power supply is shut off.
0 ∶ Clear the Up/Down frequency at stop
1 ∶ Save the Up/Down frequency at stop
2 ∶ Accept the Up/Down frequency at stop
Default: 0
Range: 0, 1, 2
Frequency
Command Bias
(Up/Down 2)
Sets the bias used to add to or subtract from
the frequency command by Up/Down 2.
Default:0.00 Hz
Min.: 0.00 Hz
Max.: 99.99 Hz
Frequency
Command
Acc./Dec Setting
(Up/Down 2 )
Sets the acceleration/deceleration times to
increase or decrease the frequency command
bias for Up/Down 2.
0 : Current Acc./Dec. Time
1 : Acc./Dec. Time 4 set in C1-06 and C1-07
Up/Down
Frequency
Command Save
Saves the frequency command from
Up/Down 1 or Up/Down 2
Default: 0.00Hz
Min.: 0.00 Hz
Max.: <5>
Sets the offset value as a percentage of the
maximum output frequency to add to or
subtract from the frequency command.
Select the offset frequency in E1-□□= 53, 54
and 55 (Offset Frequency 1 to 3).
Default: 0.0%
Min.: -100.0%
Max.: 100.0%
Sets the offset value as a percentage of the
maximum output frequency to add to or
subtract from the frequency command.
Select the offset frequency in E1-□□= 53, 54
and 55 (Offset Frequency 1 to 3).
Default: 0.0%
Min.: -100.0%
Max.: 100.0%
Sets the offset value as a percentage of the
maximum output frequency to add to or
subtract from the frequency command.
Select the offset frequency in E1-□□= 53, 54
and 55 (Offset Frequency 1 to 3).
Default: 0.0%
Min.: -100.0%
Max.: 100.0%
Automatic
operation mode
selection
0:Disabled
1:One cycle mode, when the mode is end,the
motor is stop, and then reset to restart