157
6) “Solid State motor overload protection level in percent of full-load current (120% FLA for normal
duty, 150% FLA for heavy duty).
7) “Motor overtemperature protection is not provided by the drive.
8) Type of electrical supply system (“3WYE” or “480Y/277) to which the drive shall be connected.
9) Use Copper Conductors rated 60/75 C.