5.2 Parameter List
Parameter
Name
Description
Setting Range
Group A, Initialization
A1: Basic Settings
A1-00
Retain
A1-01 <4>
Access Level
Selection
Selects access level ( edit /view)
0: View Only
Access to only parameter A1-01
1: User-Defined Parameter Access
Access to only parameter A1-01 and A2-00 to
A2-31
2: All Parameter Access
All parameters can be edited and viewed
Default 2
Min.: 0
Max.: 2
A1-02
Control Method
Selection
0: Open-Loop V/F Control
1: Closed-Loop V/F Control
2: Open-Loop Vector Control
3: Closed-Loop Vector Control
4: PM Open-Loop Vector Control
5: PM Closed-Loop Vector Control
6: Closed-Loop Torque Control
7 : Position Control - Pulse Synchronization
8: Reserved
9: SVVC mode
10: PM position control - pulse synchronization
Default: 0
Range: 0 to 10
A1-03
Reset
Resets parameter settings to defaults. After
resetting parameters, the value will become 0.
2538: Resets 2-Wire Sequence/ 50Hz / 380V
2541: Resets 2-Wire Sequence / 50Hz / 415V
2544: Resets 2-Wire Sequence / 50Hz / 440V
2546: Resets 2-Wire Sequence / 50Hz / 460V
2548: Resets 2-Wire Sequence / 50Hz / 480V
2638: Resets 2-Wire Sequence / 60Hz / 380V
2641: Resets 2-Wire Sequence / 60Hz / 415V
2644: Resets 2-Wire Sequence / 60Hz / 440V
2646: Resets 2-Wire Sequence / 60Hz / 460V
2648: Resets 2-Wire Sequence / 60Hz / 480V
3538: Resets 3-Wire Sequence / 50Hz / 380V
3541: Resets 3-Wire Sequence / 50Hz / 415V
3544: Resets 3-Wire Sequence / 50Hz / 440V
Default: 0
Range: 9999