119 
 
Chapter 6│Troubleshooting 
6.1 Alarm and Fault Displays 
Table 6.1 Alarm and Fault Displays, Causes, and Possible Solutions   
External Fault 
  ( Input Terminal S1 to 
S8 )   
1. An external device 
tripped an alarm 
2. Incorrect wiring 
3. Multi-function input 
wiring is not correct 
1. Remove the cause of the external 
fault then reset the multi-function 
input. 
2. Confirm if the signal lines is 
properly connected to the 
terminals assigned for external fault 
detection (E1-口口= 23 to 38) 
3. Confirm if E1-口口=23 to 38 is 
set to the unused terminals. 
Speed Deviation (for 
Closed-Loop Control 
Methods) 
 
The deviation between 
the pulse input speed 
feedback and speed 
command is greater than 
then level set to F1-12 for 
longer than the time set 
to F1-13.     
1. Over loaded 
2. The load is locked up 
3. Motor is being braked 
1. Increase the deceleration and 
acceleration times (C1-00 to C1-07) 
2. Check if F1-12 and F1-13 are set 
correctly. 
3. Check the motor brake and make 
sure it is released 
PID Feedback High   
 
PID feedback input is 
greater than the 
detection level set to 
b5-22 for longer than the 
detection time set to 
b5-23 
1. b5-22 andb5-23 
inappropriate setting   
2. PID feedback wiring 
incorrect 
3. Feedback sensor 
malfunction   
4. Feedback input circuit 
malfunction 
1. Confirm b5-22 and b5-23 settings 
2. Correct the wiring 
3. Replace the sensor if it is 
damaged 
4. Replace the PCB or drive.   
Contact the local distributor. 
PID Feedback Low 
 
When the PID 
feedback detection is 
enabled in b5-11, a 
1. Inappropriate setting in 
b5-12 and b5-13   
2. Incorrect PID feedback 
wiring 
3. Feedback sensor 
1. Correct b5-12 and b5-13 settings 
2. Correct the wiring 
3. Replace the sensor if it is 
damaged 
4. Contact the local distributor to