Display message R e t u r n t e m p h i g h
9 9 9 , 5 h r s
Reason
Cause:
An external heat source (CHP, heat pump etc.) has heated the return temperature above the blocking temperature.
Corrective Action:
Reduce pre heat temperature of the external heat source.
Cause:
The external heating controls suddenly close causing excessive return water temperature.
Corrective Action:
Dampen the reaction time of the external heating control system to prev ent sudden boiler temperature rise.
Display message F l u e t e m p h i g h
9 9 9 , 5 h r s
Reason The flue gas temperature has exceeded the blocking temperature.
Cause:
Heat exchanger polluted and not able to effectively transfer heat to the system water.
Corrective Action:
Check and clean the heat exchanger.
Cause:
Defective (partially shorted) flue gas sensor or sensor connection.
Corrective Action:
Cause:
There is no water in the unit while firing.
Corrective Action:
Cause:
Heat exchanger failure.
Corrective Action:
Display message A n t i c y c l e t i m e
9 9 9 , 5 h r s
Reason
Cause:
System water temperature cooling and causing a heat demand within the anti-cycling time period.
Corrective Action:
Dampen external heating system controls to slow down the cooling time of the heating medium (water).
Increase system volume to act as a buffer between the boiler circuit and heating circuit.
Cause:
Rapid opening and closing of external thermostat
Corrective Action: