Guide for troubleshooting for PS2 pump controller
Version: V210126
6.2. How to check whether there is a short circuit on the controller board input?
Write down the input voltage on the
terminal clamps of the PS2 controller
Disconnect the PV Generator from the
controller
Check the voltage of the PV Generator
If the voltage of the PV Generator raises to the expected level, replace the Power-Board. If the
voltage is still close to zero, the defective product is not the PS2 controller. Please check the PV
Generator completely (wiring/each module Voc, Isc/…).