Guide for troubleshooting for PS2 pump controller
The resistance/isolation values should be above 1 MΩ.
After the test has been performed reconnect the ribbon cable and reinstall the LED-Board
properly.
• First step: check whether there is a short
circuit between the (+) terminal and L1,
L2 or L3 (check proper polarity).
• Second step:
o contact the measuring tip to the right
MOSFET-leg (T7 – upper row left
MOSFET)
o check whether there is a short circuit
between the right MOSFET and L1, L2
or L3 (check proper polarity).