2.1 General Specifications
General specifications of XGT series are as below.
No.
Item
Specification
Related specifications
1
Operating
temperature
0℃∼ +55
-
2
Storage
temperature
-25℃∼ +70
-
3
Operating
humidity
5~95%RH, Non-condensing
-
4
Storage
humidity
5~95%RH, Non-condensing
-
5
Vibration
For discontinuous vibration
-
Frequency
Acceleration
Amplitude
Number
IEC 61131-2
5≤f< 8.4
-
3.5mm
Each 10 times in
X, Y, Z directions
8.4≤f≤150
9.8 (1G)
-
Continuous vibration
Frequency
Acceleration
Pulse width
5≤f< 8.4
-
1.75mm
8.4≤f≤150
4.9 (0.5G)
-
6
Shock
* Maximum impact acceleration:147 m/s
2
(15G)
* Authorized time: 11 m/s
* Pulse wave : Signal half-wave pulse (Each 3 times in X,Y,Z directions)
IEC 61131-2
7
Noise
Immunity
Square wave impulse noise
AC : ±1,500V
DC : ±900V
Test specification
LS ELECTRIC
Electrostatic discharging
Voltage: 4kV (Contact discharge)
IEC 61131-2,
IEC 61000-4-2
Radiated electromagnetic
27 ~ 500 MHz, 10 V/m
IEC 61131-2,
IEC 61000-4-3
Fast
Transient
/burst
noise
Class
Power
module
Digital/Analog I/O
communication interface
IEC 61131-2,
IEC 61000-4-4
Voltage
2 kV
1 kV
8
Ambient
conditions
No corrosive gas or dust
-
9
Operating
height
2,000 m or less
-
10
Pollution
degree
2 or less
-
11
Cooling type
Natural air cooling
-
1) IEC (International Electrotechnical Commission)
: An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic fields, publishes international standards and manages applicable estimation system related
with.
2) Pollution degree
: An index indicating pollution degree of the operating environment which decides insulation performance of the
devices. For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution
occurs. However, this state contains temporary conduction due to dew produced.