Chapter 5 High-speed Link Setting
5-1
Chapter 5 High-speed Link Setting
High-speed link specifies the Send/Receive device area and data size between CPU module and the
communication module by XG5000.
High-speed link can be set the function as shown below.
Communication
module
setting
Communication
module setting
Max.: 0 ~ 7
Setting range is different from CPU module.
Max.: 0 ~ 11
Setting range is different from Base type.
Communication
period setting
(Period type)
Select among 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s, 10s.
- Default setting: 200 ms
Output data setup
in case of
emergency
Keep the previous output status.
Keep the previous output status.
High-speed
link
block setting
Send: Data is transmitted from master module to slave module.
Receive: Data is transmitted from slave module to master module.
Slave station number (Range: 0 ~ 63)
It is not used with Rnet I/F module.
Read area
(From Master to
Slave module)
Head address of the sending device
Usable device: P, M, K, F, T, C, U, Z, L, N, D, R, ZR
Head address of the sending device
Usable device: A, M, I, Q, R, W, F, K, L, N, U
Input/Output point of slave module is displayed Byte.
- If input module point is less than 8 bit, it is processed 1 Byte.
Save area
(From Slave to
Master module)
Head address of the receiving device
Usable device: P, M, K, F, T, C, U, Z, L, N, D, R, ZR
Head address of the receiving device
Usable device: A, M, I, Q, R, W, F, K, L, N, U
Input/Output point of slave module is displayed in Byte.
- If input module point is less than 8 bit, it is dealt with 1 Byte.
RS-232C or USB Port of CPU module
It can control regardless of position of Run mode switch (Run, Stop) of CPU module.
29760 points (31 blocks * 120 bytes)
63 (Setting Range : 0~62)
Number of High-speed link
setting
▶
When High-speed link is edited, parameter has to download again.
▶
High-speed link is used per a communication module.
▶
CPU module saves the written parameter (Standard, High-speed link, P2P).
When CPU module is exchanged, parameter in XG5000 has to back-up and then the parameter has to
write in CPU module again.