EasyManua.ls Logo

LS ELECTRIC XGT Series - Performance Specifications

LS ELECTRIC XGT Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 Specifications
2-2
2.2 Performance Specifications
Specifications for system configuration of Rnet I/F module are as described below.
Please refer to the table below for system configuration.
1) XGL-RMEA/B Performance Specifications
Item
Specifications
Transmission Speed
1Mbps
(Rnet I/F modules common)
Max. Tx distance
Max. 750m
Connection Cable
Twisted pair shielded cable
- Standard: LIREV-AMESB 1Px22AWG (7/0.254):LS Cables
- Moving: CAN Bus Drag Chain, UL (1x2x0.34mm²): Helukable
Maximum stations
connected
Network
Master station 1[station no:0(fixed)] +
Slave station 31[station no:1~63]
= Max. 32 stations
(In case of 32 stations, you have to use repeater.)
- Only 1 master is available in the network.
Diagnostic function
XG5000 : High Speed Link Monitoring
System characteristic
Available detachment and attachment of slave
module during communication
Terminating resistor()
110(5%,1/2W)
Master/Slave operation
Only available as Master
XG5000
(HS Link)
Data Processing unit
Byte
Tx/Rx cycle
Selection among 20ms, 50ms, 100ms, 200ms,
500ms, 1s, 5s, 10s(default :200ms)
Max. Communication
points.
3,720bytes(slave 31stations * 120bytes/station)
Max. Block number
63(setting range : 0~62)
Max. points by Block
120 Byte(60words)
Max. Tx. Block number
32 Blocks
HS Link number
Max. 12
Specification
Max. module mounted
12 modules(Main Base + Extension Base)
Internal current
consumption
410mA
Weight
115g