Chapter 3 Installation and Test Operation of the Product
3-1
Chapter 3 Installation and Test Operation of the Product
3.1 Precautions for Installation
3.1.1 Precautions for installation
For system configuration through Rnet I/F module, carefully make sure of the following items prior
to installation.
1) Check the basic factors for necessity of configuring the system and select an appropriate
communication module.
2) Select the cable to be used for this communication module (surely use the standard cable).
3) Before the communication module is installed, check with any foreign material on the base
connector the module will be installed on and any damage on the connector pin of the module.
4) For installation of the module, exactly insert the protuberant part at the bottom of the module with
the communication cable disconnected into the base groove and then apply enough strength
until its top is locked up with the locking device of the base. If the lock is not applied, it may
cause an error on the interface with CPU.
3.2 From Setting to Operation
The sequence of the product from installation to operation will be described below. After the product
installation is complete, install and configure the system to be operated as specified in the following
sequence.
Operation Sequence
Install Rnet I/F module on the base.
Check the applicable base/slot position for correct installation on the basic base.
Connect Rnet I/F module with remote I/O by means of cable.
Connect the cable and process terminal resistance.
With power On, check the LED status of the communication module.
Check if the interface of the communication module is normal with CPU.
Specify High-speed link parameters in XG5000.
Specify parameters applicable to network configuration in XG5000 and download
the parameters.
Let link enabled in XG5000.
Start Run
Notes
1) The station number of the master module is set to 0.
2) The station number of the remote I/O should not be set to 0.