Chapter 2 Specifications
2-3
2) GOL-RR8T Performance Specifications
- Communication Specifications
Item
GOL-RR8T
Communication method
Rnet
Communication ports (Master : Slave)
1 : 8
Max. Slave stations / All repeaters
32 Stations
Number of Max. slaves when using repeater /a Network
XGL-RMEB
XBL-RMEA
63 Stations
31 Stations
Max. repeaters /a Network
(Repeaters can be connected to trunk line only)
2 Modules
Communication speed
1Mbps
Max. transmission distance /
Each repeater port
LIREV-AMESB 1Px22AWG
(7/0.254)_LS Cable
300m
CAN Bus Drag Chain, UL
(1x2x0.34mm²)_Helukable
600m
Master Max. transmission distance
(Master + Slave or Master + Repeater)
750m
Network max. transmission distance
(Master + Repeater + Slave)
- LIREV-AMESB 1Px22AWG: 1.05km
- CAN Bus Drag Chain: 1.35km
Weight
580g
< Network configuration using repeaters >
3)
1) In order to minimize the reflected wave, the line connecting with the repeater should
Use more than 1m cable.
2) Repeater hub 8port module in the user's manual is called a repeater module for
convenience.
Note

Related product manuals