EasyManua.ls Logo

LS ELECTRIC XGT Series - Page 54

LS ELECTRIC XGT Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A-3
Notes
HS link No.
L area address
Remarks
2
L000500~L00099F
Compared with HS link of 1 in [Table 1], other HS link station number’s
flag address will be simply calculated as follows;
Calculation formula:
L area address = L000000 + 500 x (HS link No. 1)
In order to use HS link flag for program and monitoring, use the flag map
registered in XG5000 for convenient application.
3
L001000~L00149F
4
L001500~L00199F
5
L002000~L00249F
6
L002500~L00299F
7
L003000~L00349F
8
L003500~L00399F
9
L004000~L00449F
10
L004500~L00499F
11
L005000~L00549F
Example) K as a block number is displayed through 8 words by 16 for 1 word for the information of 128 blocks
from 000 to 127.
For example, block information of 16~31, 32~47, 48~63, 64~79, 80~95, 96~111, 112~127 will be displayed in
L00011, L00012, L00013, L00014, L00015, L00016, L00017 from block 0 to block 15 for mode information
(_HS1_MOD). Thus, the mode information of the block No. 55 will be displayed in L000137.

Related product manuals