Chapter 7. Usage of Various Functions
7-37
(3) In case of using combined function of PID operation and auto tuning
(a) PID operation explanation (with A/T function)
Measure current temperature by RTD module then digital conversion value(0 ~ 4000) is stored.
PID7AT instruction will calculate manipulate value (MV : 0 ~ 4000) based on the SV and PV from RTD module
and output the value in range of 0~4000 to the D/A conversion module.
The END bit of auto tuning status device will be 1 when the auto tuning is completed, and the calculate P, I, D
constants are saved respectively in the designated value. These values become the P, I, D control constant.
Program to execute the PID operation when the END bit becomes 1.
D/A conversion modules convert the manipulate value to analog signal (4~20mA) and input it to the actuator.
(b) PID Auto Tuning Parameter
Target value (for G7F-RD2A)
- 1300(60),1350(70),1400(80),1500(100)
Scan Time: 0.5 sec(input ‘5’)
Current value: %MW4104 (conversion value of the RTD module’s channel 0)
Ripple Type: Relay Method
(c) Auto tuning parameters
Scan Time: 0.5 sec (input ‘5’)
Operation Mode: 0 (Auto)
Output Limit Value: Max: 4000, Min: 0
Man OP range: 0 (Operation mode is set to ‘Auto’)