Chapter 7. Usage of Various Functions
7-64
4) Scaling function (for G7F-DA2I)
Scaling is the function that changes the offset and gain value for an easy operation.
Changing method is as below.
Scaling conversion value
800
4000
3200)value input (Digital
+
×
=
Example) Digital value 1000 input in a range of 0 ~ 20
Before the scaling conversion (current range 0 ~ 20mA):
5mA
4000
201000
4000
20)value input (Digital
=
×
=
×
After the scaling conversion (current range 4 ~ 20mA):
8mA5μA1600800
4000
32001000
800
4000
3200)value input (Digital
=×=+
×
=+
×
5) Wiring
(1) Caution for wiring
Make sure that external input signal of the mixture module of AC and analog I/O is not affected by induction noise or
occurs from the AC through using another cable.
Wire is adopted with consideration about peripheral temperature and electric current allowance. For wire, thicker than
AWG22 (0.3 ) one is recommended.
If wire is put near to high temperature radiated device or contacted with oil for a long time, it may cause of electric
leakage so that it gets broken or miss-operation during wiring.
Be sure to connect with care of polarity while connecting to external 24V DC power supply.
In case of wiring with high voltage line or generation line, it makes induction failure so then it may cause of miss-
operation and out of order.
4000
0
0㎃
20
4000
0
4㎃
20
Resolution: 20 /4000 = 5
Resolution: 20 /3200 = 6.25