Chapter 8. Communication Functions
8-36
Select ‘OK’ in the communication parameter window to complete the parameter settings.
Program description
- Increase the value of %MW000 at the rising edge at every second.
- Communication is executed following the parameter settings.
(2) Slave station’s parameter settings
Station No: Select 31 (0 ~ 31 available)
Baud rate: Select 19200
(1200, 2400, 4800, 9600, 19200, 38400, 57600)
Parity bit: None (None, Even, Odd available)
Data bit: Select 8 (7, 8 available)
Stop bit: Select 1 (1,2 available)
Communication channel:
Select RS-232C Null Modem or RS-422/485
Timeout in master mode: Select 500ms
(10 ~ 2000ms available)
Protocol and mode: Select Dedicated Slave
(Master/Slave)