Chapter 2 Specifications
7
Chapter 2 Specifications
2.1 General Specifications
[Table 2-1] shows general specification of XGB series.
No. Item Specifications References
1 Operating Temp. 0 +55℃∼
2 Storage Temp. -25 +70℃∼
3 Operating Humidity 5 95%RH, non-condensing.
4 Storage Humidity 5 95%RH, non-condensing.
Occasional vibration -
Frequency Acceleration Amplitude Sweep count
10 f < 57Hz 0.075mm
57 f 150Hz 9.8m/s
2
{1G}
Continuous vibration
Frequency Acceleration Amplitude
10 f < 57Hz 0.035mm
5 Vibrations
57 f 150Hz 4.9m/s
2
{0.5G}
10 times for
each X, Y, Z
axis
IEC61131-2
6 Shocks
• Maximum shock acceleration : 147 (15g)
• Duration time: 11
• Pulse wave : half sine pulse( 3 shocks per axis, on X,Y,Z axis)
IEC61131-2
Square wave Impulse
noise
±900V
LSIS internal
standard
Electronic discharge Voltage: ±4 (Discharge by contact)
IEC61131-2
IEC610004-2
Radiated
electromagnetic field
noise
27~500MHz, 10V/m
IEC61131-2
IEC61000-4-3
Item Power supply
Digital I/O
Analog I/O
Communication Interface
7 Noise Immunity
Fast transient & Burst
noise
Voltage 2kV
1kV
IEC61131-2
IEC61000-4-4
8 Atmosphere Free of corrosive gases and excessive dust
9 Cooling method Natural air-cooling
10 Altitude Up to 2,000m
11 Pollution degree Less than 2
[Table 2-1] General specification
Remark
1) IEC (International Electro-technical Commission): An international civilian institute who establishes international standards in the
area of electric and electronics.
2) Pollution degree: An indicator, which indicates pollution degree, which determine insulation performance of equipment.
* Pollution degree 2: Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductively caused by
condensation shall be expected.