45
4011 RW 0...4
Erasing of watt-hour meters:
0 – without changes,
1- erase active energy,
2 – erase reactive energy,
3 – erase energy of harmonics,
4 – erase all energy.
0
4012 RW 0,1
Erasing of mean active power
P
AV
0
4013 RW 0,1
Erasing of the averaged power
archive
0
4014 RW 0,1 Erase min and max 0
4015 RW 0,1 .. 35
Quantity on the alarm relay output
(code acc. to the table 6)
24
4016 RW 0 ... 9
Output type: 0 – n-on, 1– n-oFF,
2 – on, 3 - oFF, 4 – H-on,
5 – H-oFF, 6 - A3non, 7 - A3nof,
8 - A3_on, 9 - A3_of
0
4017 RW
-1440..0..
1440 [
o
/oo]
Lower alarm switching value 990
4018 RW
-1440..0..
1440 [
o
/oo]
Upper alarm switching value 1010
4019 RW 0...900 s
Delay of the alarm switching ( for
quantity AL_n = P_ord – rgister
4015 =35, the delay occurs only
when the alarm is switched on.
0
4020 RW
1..2000
[10uA]
Alarm signaling support 0
4021 RW 0..2
Quantity on the continuous output
no 1/ code acc. to the table 6 /
24
4022 RW 0,1
Continuous output type:
0 – 0...20 mA;
1 – 4...20 mA
0
4023 RW
-1440..0..
1440 [
o
/oo]
Lower value of the input range in
[
o
/oo] of the rated input range.
0
4024 RW
-1440..0..
1440 [
o
/oo]
Upper value of the input range
in [
o
/oo] of the rated input range.
1000