46
4026 RW
1..2000
[10uA]
Upper output range value of the
output [10 uA]
2000
4027 RW 0..2
Manual switching of the analog
output 1:
0 – normal work,
1 – set value from the register 4026,
2- set value from the
register 4027,
0
4028 RW
0..24
[mA]
Analog output value when error 24
4029 RW
1000..
20000
Number of impulses for the
impulse output
5000
4030 RW 1..247
Address in the MODBUS
network
1
4031 RW 0..3
Transmission mode: : 0->r8n2,
1->r8E1, 2->r8o1, 3->r8n1
0
4032 RW 0..3
Baud rate: 0->4800, 1->9600
2->19200, 3->38400
1
4033 RW 0.1
Bring up to date the transmis-
sion parameter change
0
4034 RW 0..2359 Hour *100 + Minutes 0
4035 RW
101..
1231
Month * 100 + day 101
4036 RW
2009..
2100
Year 2009
4037 RW 0,1
Record of standard parame-
ters (together with the reset of
energy and min, max, averaged
power)
0
4038 R 0..15258
Imported active energy, two
older bytes
0
4039 R 0.. 65535
Imported active energy, two
younger bytes
0
4025 RW
-2000..0..
2000
[10uA]
Lower output range value of the
output [10 uA]
0