2-4
CDA3000 Operation Manual
2  Mechanical installation
2.4 Cold plate
 
 
Figure 2.2 Mounting clearances (see Table 2.3)  
Step Action Comment
1
Mark out the positions of the tapped 
holes on the backing plate or the cooler. 
Cut a tap for each fixing screw in the 
backing plate. 
Dimensional drawings/hole 
spacing - see Table 2.3.
The tapping area will provide 
you with good, full-area contact.
2
Clean the contact surface and coat it 
thinly and evenly with heat transfer 
compound.
The contact surface must be 
metallically bright. 
3
Mount the inverter module vertically on 
the backing plate or cooler. Tighten all 
screws to the same tightness.
Pay attention to the mounting 
clearances! Size of cooling area 
- see Table 2.4.
4
Mount the other components, such as 
the mains filter, line choke etc., on the 
backing plate.
Mains filter max. 20 cm below 
the inverter module
5
Continue with the electrical installation in 
section 3.
F
E
G
F
E1
UM-xxxx
CM-xxxx