Sequence of Operation Details
zPidFlow (%)
49.9
MaxAFpos
(AV3) 100%
zActMod (AO2)
100
Cooling
Independent Pressure Control
VAV_Type (MSV27) = 2
MinAFpos
(AV4) 15%
0
HtgClgMode (
M
SV2
6
) =
2
(
cool)
Control (%)
RoomT_Loc (MSV17):
1x Tzone.
PidRoomT_Clg
2x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Clg
Tzone2.
PidRoomTz2_Clg
Average.
(PidRoomT_Clg + PidRoomTz2_Clg) / 2.0
Maximum Htg
MIN(PidRoomT_Clg, PidRoomTz2_Clg)
Maximum Clg
MAX(PidRoomT_Clg, PidRoomTz2_Clg)
3x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Clg
Tzone2.
PidRoomTz2_Clg
Tzone3.
PidRoomTz3_Clg
Average.
(PidRoomT_Clg + PidRoomTz2_Clg + PidRoomTz3_Clg) / 3.0
Maximum Htg
MIN(PidRoomT_Clg, PidRoomTz2_Clg, PidRoomTz3_Clg)
Maximum Clg
MAX(PidRoomT_Clg, PidRoomTz2_Clg, PidRoomTz3_Clg)
PidRoomT_Clg On/Off
ON
MinAFpos_Clg
(AV6) 25%
MinAFpos
(AV4) 15%
0
HtgClgMode (MSV26) = 2
(
cooling)
AUX mode ON OFF C
ooling (A
to E)
PidRoomT_Clg AO
100
MinAFpos_Clg
(AV6) 25%
MinAFpos
(AV4) 15%
0
HtgClgMode (MSV26) = 2
(
cooling)
AUX analog Cooling (A t
o E)
Dependent Pressure Control
VAV_Type (MSV27) = 1
zPidFlow (%)
49.9
MaxAFpos
(AV3) 100
CFM
zActiveFlowSP (AV2)
100
MinAFpos
(AV4) 0
CFM
0
HtgClgMode (MSV26) = 2
(
cool)
PidRoomT_Clg On/Off
MinAFpos_Clg
(AV6) 30 CFM
zActiveFlowSP (AV2)
MinAFpos
(AV4) 0
CFM
0
HtgClgMode (MSV26) = 2
(
cooling)
AUX mode ON OFF C
ooling (A
to E)
PidRoomT_Clg AO
100
MinAFpos_Clg
(AV6) 30 CFM
zActiveFlowSP (AV2)
MinAFpos
(AV4) 0
CFM
0
HtgClgMode (MSV26) = 2
(
cooling)
AUX analog Cooling (A t
o E)
ON