DIP switches DS2 configures the MS/TP address
The Values of the On Switches adds up
Possible Address : 1 - 127
DIP switches DS1 configures the Baud Rate (BPS)
Switches Configuration : Off = 0, On = 1
Available baud rates :
010 - 9600 BPS, 110 - 19200 BPS, 001 - 38400 BPS, 011 - 76800 BPS
EOL jumper: MS/TP Network end of line
EOL jumper: Tzone Netwotk end of line
These jumpers are used to configure the analog input:
Left = mA 4 - 20 mA or 0 – 20 mA
= Thermistor 10K Type 3 (std) or Type 2Middle
Right = Vdc 0 – 10 V or 2 – 10 V
AO1 and AO2 Switches allow analog output bypass control when “HAND” is selected
Switch Left = AUTOMATIC
Switch Right = HAND (manual)
Counterclockwise for 0% (0V)
Clockwise for 100% (10V)
Installation
Jumper Settings
JP11
JP10