Installation
Jumper Settings
When used in conjunction with jumpers, switches SW1 to SW4 allow binary output
bypass control and selection:
SW4 Overrides BO1
SW3 Overrides BO2
SW2 Overrides BO3
SW1 Overrides BO4
Replaceable TR5R Fuse, Time-Lag type, 2.0 A
Littelfuse 37212000411
Actuator driver connector:
1 = 24V, 2 = A0 , 3 = COM, 4 = Open , 5 = Close
Manual operation of the actuator
Hold the switch in the up or down position for 2 seconds, until a beep sounds.
This will completely force the actuator clockwise or counter clockwise for one hour.
A beep will sound every 5 seconds.
The bypass will automatically be cancelled after one hour.
To cancel before the hour, hold the switch in the up or down position for 2 seconds until a beep sounds.
SW7
LEFT = manual On (Hand)
CENTER = automatic
RIGHT = manual output Off
Isolated contacts
Internal 24Vac supply
**recommend
using pilot relays in any application utilizing Binary outputs
as switching loads. **
24V
24V
JP2/
JP3
JP4/
JP5
BO1
COM
BO2
BO3
COM
BO4
LOAD
LOAD
LOAD
LOAD
COM
24Vac
24Vac
COM
24Vac
24Vac
JP2/
JP3
JP4/
JP5
LOAD
LOAD
LOAD
LOAD
BO1
COM
BO2
BO3
COM
BO4
24Vac
24Vac Supply
24Vac
24Vac
24Vac
www.lynxspring.com