Binary Values
Object
Instance
Description Default value
Tags
Inactive_Text Active_Text
Object name
BV0
ActRotation Actuator rotation direction Direct Cfg Direct Reverse
BV1
FanStatus FanStatus On Status Off On
BV2
DewPtHL Dewpoint Temperature High Limit
--- User 32°F (0°C) 122°F (50°C)
BV3
OccSched Occupancy schedule Day Clg Night Day
BV4
OvrStatus Occupancy override status Inactive Status Inactive Active
BV5
Cond_Status Condensation Status from input
---
Status
Normal Detected
BV10
SaveAndRestart Saves Objects to Flash and restart
Off
Cmd
Off On
Please note that objects tagged as:
• Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
• User: represent properties or objects that are typically manipulated by users of the controller
• Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
• Cmd: represent objects that can be controlled directly by other BACnet external process
www.lynxspring.com