Analog Values
Please note that objects tagged as:
• Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
• User: represent properties or objects that are typically manipulated by users of the controller
• Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
• Cmd: represent objects that can be controlled directly by other BACnet external process
Object
Instance Object name
Default value
Tags
Minimum
range value
Maximum
range value
AV66
RoomCO2SP
Description
Room CO2 Setpoint ---
User 0PPM
2000PPM
AV67
RoomCO2Dem Room CO2 demand
---
Status
0%
100%
AV68
DewPtHL Dewpoint Temperature High Limit
--- User 32°F (0°C) 122°F (50°C)
AV69
DewPtLL Dewpoint Temperature Low Limit
--- User 32°F (0°C) 122°F (50°C)
AV70
DewPoint Dewpoint Calculated Temperature
---
Status
32°F (0°C) 122°F (50°C)
AV71
DewPtOffset Dewpoint Offset to close cooling valve
---
Status
32°F (0°C) 122°F (50°C)
AV72
Chillwater Chilled Water Reading
---
Status
32°F (0°C) 122°F (50°C)