Sequence of Operation Details
Aux C Heating
AuxC_Out (AV48)
PidHtg (%)
Var1(AuxC_Out) Var2(AuxC_Out)
80% 100%
AuxC_Out (AV48)
80%
Var1(AuxC_Out) Var2(AuxC_Out)
100%
PidHtg (%)
AuxC_Out (AV48)
PidClg
Var1(Aux
C_Out) Var2(AuxC_Out)
80% 100%
Aux C Cooling
AuxC_Out (AV48)
80%
Var1(AuxC_Out) Var2(AuxC_Out)
100%
PidClg
PidCl
g (%)
RoomT_Loc (MSV17):
1x Tzone.
PidRoomT_Clg
2x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Clg
Tzone2.
PidRoomTz2_Clg
Average.
(PidRoomT_Clg + PidRoomTz2_Clg) / 2.0
Maximum Htg
MIN(PidRoomT_Clg, PidRoomTz2_Clg)
Maximum Clg
MAX(PidRoomT_Clg, PidRoomTz2_Clg)
3x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Clg
Tzone2.
PidRoomTz2_Clg
Tzone3.
PidRoomTz3_Clg
Average.
(PidRoomT_Clg + PidRoomTz2_Clg + PidRoomTz3_Clg) / 3.0
Maximum Htg
MIN(PidRoomT_Clg, PidRoomTz2_Clg, PidRoomTz3_Clg)
Maximum Clg
MAX(PidRoomT_Clg, PidRoomTz2_Clg, PidRoomTz3_Clg)
PidHtg (%)
RoomT_Loc (MSV17):
1x Tzone.
PidRoomT_Htg
2x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Htg
Tzone2.
PidRoomTz2_Htg
Average.
(PidRoomT_Htg + PidRoomTz2_Htg) / 2.0
Maximum Htg
MIN(PidRoomT_Htg, PidRoomTz2_Htg)
Maximum Clg
MAX(PidRoomT_Htg, PidRoomTz2_Htg)
3x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Htg
Tzone2.
PidRoomTz2_Htg
Tzone3.
PidRoomTz3_Htg
Average.
(PidRoomT_Htg + PidRoomTz2_Htg + PidRoomTz3_Htg) / 3.0
Maximum Htg
MIN(PidRoomT_Htg, PidRoomTz2_Htg, PidRoomTz3_Htg)
Maximum Clg
MAX(PidRoomT_Htg, PidRoomTz2_Htg, PidRoomTz3_Htg)