Multi-State Values
Object
Instance
FCU
Object name
Description
Tags
Default value State texts
MSV19
USsupplyT_Loc Upstream supply loc. (from main fan)
Cfg
AI-1
None
AI-1, AI-2, AI-3 or AI-4
External
MSV20
DSsupplyT_Loc Downstream supply loc (after reheat)
Cfg
None
None
AI-1, AI-2, AI-3 or AI-4
MSV21
FanStatus_Loc Fan status location
Cfg
None
None
AI-1(BI), AI-2(BI), AI-3(BI) or AI-1(BI)
External
MSV22
Motion_Loc Motion sensor location
Cfg
None
None
NO, AI-1 (BI) / NC, AI-1 (BI) / NO, AI-2 (BI) / NC, AI-2 (BI)
NO, AI-3 (BI) / NC, AI-3 (BI) / NO, AI-4 (BI) / NC, AI-4 (BI)
External
MSV23
Sched_Loc Scheduler location
Cfg
None
None
AI-1(BI), AI-2(BI), AI-3(BI) or AI-4(BI)
External
MSV24
OccMode Occupancy mode
Status
Occupied
Unoccupied
Occupied
Standby
MSV25
ChOver_Type Changeover type
Cfg
RoomT°+Offset
None
Constant
RoomT°+Offset
Please note that objects tagged as:
Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
User: represent properties or objects that are typically manipulated by users of the controller
Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
Cmd: represent objects that can be controlled directly by other BACnet external process
www.lynxspring.com