DRIVE SETUP AND ADJUSTMENT
46
Drive Setup &
Adjustments
Software Operating Features
The DSD 412 is configured by software to
operate geared and gearless elevators and
lifts. The SA407 Drive Control software
contains desirable feature improvements
from the previous version, SA274. Basic
features include...
User choice of operating speed reference
External analog reference follower
Serial link reference follower
Internal reference generator with S-Curve
smoothing, to one of 7 preset speeds (8
speeds including zero)
User choice of ft/min or m/sec speed
programming and display units
User choice between binary or progressive
relay selected internal preset speeds.
Selectable input control logic for Run-Up /
Run-Down or Run / Direction relay control
with internal preset speeds.
MagneTek exclusive E-Reg, elevator
velocity regulator
Simplified analog or serial link Pre-Torque
operation to prevent roll-back on starts
Controlled Current Ramp-Down to prevent
elevator brake thumping at stops
Internal frequency notch filter to reject rope
resonance interference.
Closed loop motor field current regulator
with simplified motor field weakening and
stand-by adjustments
Maintainance Armature Voltage Feedback
mode.
User selectable choices for relay logic
output, including:
Drive OK / No Faults relay
Invert/Noninvert Alarms Relay
Drive operating, OK to release brake
Car above/below speed X threshold
Car above/below Zero speed threshold
Car Moving Up
Car Moving Down
Speed Error above/below X threshold for Y
seconds.
Drive Standby Power Reduction
User selectable analog diagnostic trace
outputs
Diagnostic indicator for verifying logic input
and output conditions
Analog speed reference zero adjustment
Alarm Relay to indicate important but non-
critical conditions
Motor or transformer thermostat over-
temperature
Motor Over-Load
Drive Over-Heating
Low Utility Line Input
Safety related fault trapping with
diagnostics, including:
Motor Over-Current
Motor field Malfunction
Contactor Failure
Severe Utility Line disturbances
Encoder Loss
Over-Speed Trip
User selectable automatic or external
commanded Fault Reset
New features have been arranged to be
compatible with present installations of DSD
412 using General Elevator software
SA274. The factory default settings of
software SA407 are such that it will act like
SA274 software. The user must
consciously re-program one or more
selectable features to do otherwise.
Several new useful features have been
added for SA407, plus more diagnostic
codes to help pinpoint the cause of
problems when things go wrong during
commissioning. See the appropriate
sections for explanations of Anti-RollBack,
Brake Control, Drive Standby Power
Reduction, and operation with a Uni-Polar
Analog reference. Ramp rates 3 are now
activated by external logic command at
A1TB1-10.
Motor Field Current Control
Motor field current is held at Stand-By amps
function 53 when the elevator is idle. When
the Drive Enable command is given, field
current will rise as fast as possible to the level
programmed in function 50. The drive will not
allow a drive start to occur until motor field
current rises above the threshold level set at
function 32. At high speed, the motor field
current will automatically weaken to the level
set at function 49. If the field current feedback
fails to track the field current reference by
more than 5% for 5 seconds Fault ‘413’ will be
declared. The universal motor field control
module supplied with DSD 412 can operate
motor fields from 0.2 through 40.0 ADC.