BOXER SERIES 10-20 KVA EXPLANATIONS OF LOGGING
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
3. Switch the input breaker (CB1) to closed circuit (ON) position. If there exists optional external
bypass, switch the external bypass breaker (CB5) to closed circuit (ON) position.
4. Start the UPS using the front panel.
Main Menu>Control>Password>Start
5. Check the device has switched to normal operation
mode, via front panel display LEDs and LCD panel.
6. Switch battery circuit breaker (CB4) to closed circuit (ON) position.