BOXER SERIES 10-20 KVA SAFETY AND WARNINGS
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
1.2 Clearance and Access
Clearance
There exist no air inlet or outlet grilles on the sides of 10-20 kVA UPS. All air is taken through
front and evacuated through fan grids on the back side. There must be 1 m clearance at least at
front side and 1.2 m clearance at least at rear side of UPS. There should not be permanent or
temporary use within the limits specified. Otherwise, the UPS’s performance will decrease.
Access
Operator can reach the inside of UPS through front panel on our products in the range of 10-20
kVA.Therefore, enough area must be left for operator. Furthermore, the device can be accessed
through the back side for service and maintenance. Thus, sufficient area must always be left in
the back side in order that service staff can work.
1.3 Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat
before commissioning.
Unused batteries must be charged at regular intervals. This time interval is
determined by the battery supplier. Charging batteries can be performed
periodically by connecting to a proper mains for a while.
1.4 Shipment
Carrying vehicles or handling accessories must have enough features and characteristics to carry
UPS’s weight.