62 Part Number: 040006847 12/19
Discharge Pressure High Checklist
Improper Installation
Refer to “Installation” section
Restricted Condenser Air Flow
High inlet air temperature
Condenser discharge air re-circulation
Dirty condenser fins
Defective fan motor
Improper Refrigerant Charge
Overcharged
Non-condensable in system
Wrong type of refrigerant
Other
High side refrigerant lines/component restricted
(before mid-condenser)
Freeze Cycle Discharge Pressure Low Checklist
Improper Installation
Refer to “Installation” section
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
High side refrigerant lines/component restricted
(before mid-condenser)
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.