Part Number: 040006847 12/19 69
Check Procedure
n
Warning
Disconnect electrical power to the entire ice machine
before proceeding.
Make sure bulb is inserted correctly 35.5 cm (14") in the
bulb well. Disconnect the wires from the bin thermostat
and check the resistance across the terminals.
No Ice on Bulb Ice on Bulb Result
Closed (O) Open (OL) Thermostat is good
Open (OL) Closed (O) Replace thermostat
NOTE: After covering/uncovering the bulb holder with ice,
wait at least 3 minutes to allow the thermostat to react
(Open/Close).