S
ection
1
Single-Phase: 120 to 300 Vac
Frequency Range: 225 to 325 Hz
Generator Voltage Sensing
Type: 1-phase/3-phase, 4 ranges,
Range 1: 120 Vac (100 to 140 Vac)
Range 2: 240 Vac (200 to 280 Vac)
Range 3: 480 Vac (400 to 560 Vac)
Generator Current Sensing
Type: 1-phase (BØ), 50/60 Hz
Rating: 5 Aac maximum continuous
Interrogation Voltage: 13 Vdc
Unit/Parallel Control: 52L, 52M
Rated Load: 7 Aac/7 Adc continuous
Make: 30 Aac/30 Adc, carry for 0.2
Operating Voltage: 240 Vac/250 Vdc maximum
Continuous Rating: 75 Vdc, 3.0 Adc
200 Vac Power Input: 150 Vdc, 7.5 Adc
Adjustment Range: See generator voltage sensing
Voltage Regulation: ±0.25% over load range at rated
power factor and constant generator
Temperature Drift: ±0.5% for a 40°C change
Characteristic: Slope from 1 to 3PU is adjustable in
FCR (Manual) Operating Mode
Adjustment Range: 0 to 3 Adc
VAR Operating Mode (Optional)
Adjustment Range: 100% to –100%
PF Operating Mode (Optional)
Adjustment Range: 0.6 lead to 0.6 lag
Modes: Reactive Droop and
Reactive Differential (cross-current)
Adjustment Range: 0 to 10%
*Burden can exceed 1 VA if external resistors are added to
Interface: Full Duplex RS-232
Connection: DB-9 connector on rear panel
Field Overvoltage Protection
Adjustment Range: 0 -250 Vdc
Fixed Setting: 15 seconds
Field Overcurrent Protection
Adjustment Range: 0 to 6.5 Adc
Adjustment Range: 0 to 10 seconds
Generator Overvoltage Protection
Adjustment Range: 105 to 120% of setpoint
Fixed Setting: 0.75 seconds