CD 30 ÷ 520
36
CD
Models
60 120 180 240 300 360 420 480
High-pressure
switch
Cut off
Close
MPa
Reset automaticallyˈunadjusted
3.3
2.4
For compressor
Low-pressure
switch
Cut off
Close
MPa
Reset automaticallyˈunadjusted
0.03
0.15
Temp Sensor inside the
digital compressor
-
Controlled by micro- controller
When the Temp. is lower than 125ć, compressor
will not work. When the Temp. is higher than 125
ć, the capacity output of digital compressor will
decrease to 40%. When the Temp. is higher than
140ć,compressor will stop. After the malfunction
disappear, compressor will restart 3 minutes later.
Over-current protection A 18
Heating belt
Capacity
W
Each compressor has one
40
Discharge Temp.
Protection
Cut off
Close
ć
130
90
Anti-freeze Protection
Switch
ć
Controlled by micro- controller (one every cycle.)
3
Notices
Because the water pump is under the control of main unit, it is forbidden to start the pump
by the main unit when cleaning water system pipeline.
Before finishing draining water out from pipeline, it is forbidden to start unit.
Install the water flow switch correctly; otherwise water shortage accident will happen.
During test-running, do not restart the unit by manual in 4 minutes after the unit stops.
In the season when the unit needs to be frequently used, don’t switch off power after the
unit stops. Otherwise, the compressor can’t be preheated, which may damage the
compressor.
After a long time without electrifying, please pre-electrify the unit 12 hours in advance to
preheat the compressors.