EasyManua.ls Logo

Maytag PSA4BG024K - Preparation; Slab Mounting; Roof Mounting

Maytag PSA4BG024K
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
PREPARATION
Before proceeding with installation of iQ air conditioning
equipment, consult with the distributor and homeowner to
confirm that the equipment listed on the order is what was
ordered, and that it matches labeling on the equipment
packaging.
Determine (including consultation with the homeowner) the
intended/preferred location for placement of the compressor/
outdoor coil unit. Unit envelope dimensions are shown in
Figure1.
This air conditioner is designed for outdoor installation only.
Unit placement must take into consideration the following
clearances:
• Aminimumof12inchesmustbeprovidedbetweeneach
of the four sides and any solid barrier or wall which might
blockfreeinletairowintothecoil.Aminimumclearance
of 18 inches is required between multiple units.
• Thecorneroftheunitcoveredbythecontrolaccesscover
must be clear enough to allow comfortable access by a
serviceperson.
• Thetopoftheunitmustbeopenandunobstructedtoprevent
recirculation of outdoor fan discharge air, particularly for air
conditioning usage. A minimum distance of 4 feet overhead
clearance is recommended. Do not locate the unit in a pit
with high walls on all sides.
Locatetheunitawayfromoverhangswhichwouldallowwater
runoff or ice to fall directly onto the air conditioner. In low
temperature climates, place the unit where it is not directly
in prevailing winds. Avoid placing the air conditioner near
sleeping quarters or windows.
Slab Mounting
• Thepreferredunitmountingisonanoutdoorslab(concrete
or plastic), on the ground, in an area with good drainage
unlikelytobeaffectedbyheavyrunoff,groundsettling,or
deep snowdrift accumulation.
• Thesupportslabshouldbelevel.Makesurethatthedrain
holes in the bottom of the unit are not obstructed.
Roof Mounting
The method used for roof mounting should be designed so
as not to overload roof structures nor transmit noise to the
interior of the structure. Refrigerant and electrical lines should
be routed through suitably waterproofed openings to prevent
leakingintothestructure.Makesurethattheroofstructure
can adequately support the weight of the equipment. Consult
local building codes for rooftop installations.
After a location has tentatively been selected, trace routing
of new (or pre-existing) refrigerant lines (two), and power and
control wiring. See further discussion below.
• Maximumrecommendedlengthforrefrigerantlines:100
ft.
• Maximumelevationdifference,compressorbasetoindoor
coilbase(compressorhigherorlower):50feet.NOTE: An
oiltrapisrequiredforelevationsexceeding50feet.
• Refrigerant lines should NOT be buried (in concrete or
otherwise).
• Refer to the Application GuidelineforRefrigerant Lines
Over75Feetdocument044B-0600,forpipingdetails.
Once the above information has been confirmed and potential
questions regarding location, refrigerant line routing, and
wireroutinghavebeenresolved,proceedwithunpackingthe
equipment. It is strongly recommended that inspection of the
hardware be performed prior to bringing it to the installation
site. Inspect for cosmetic as well as functional damage (such
as obvious holes or gaps in tubes and joints, cut or pinched
wires or wire insulation).
Verify that the iQ Drive
®
airconditionerunitpackageincludes
thefollowing:
• Coil/compressor/controlunit.
• Packetcontaininginstallationinstructionsandonelter-
drier.
Figure 1. Unit Envelope Dimensions
EXTERIOR WALL
CONTROL
PANEL
24”
For Service
Access
12”
12”
12”

Related product manuals