MC100
Mobile programmable gateway
MC Technologies GmbH, Kabelkamp 2, 30179 Hannover, Germany
Tel: +49511 67 69 99-0, Fax: +49511 67 69 99-150, Website & Shop: www.mc-technologies.net, Email: info@mc-technologies.net
35
Example: Output of 6mA at OI1
Command: echo 6000 > /sys/senst2_ADC/adc_output/adcoutput0/value
Response: none
Function: Output of a current (v1.0.5 and later)
/sys/senst2_board/output/1
/sys/senst2_board/output/2
Note: Conversion from mA to value to be supplied
Formula: Value = Current in mA * 1000
Example: Current = 6mA Corresponds to Value = 6000
PT100 / PT1000 Inputs 11.6.6
Function: Reading a resistance/ temperature value (v1.0.4 and older)
/sys/senst2_rtd/rtd0/value
/sys/senst2_rtd/rtd1/value
/sys/senst2_rtd/rtd2/value
/sys/senst2_rtd/rtd3/value
Example: Read the value at RTD1
Command: cat /sys/senst2_rtd/rtd0/value
Response: e.i. 100000
Function: Reading a resistance/ temperature value (v1.0.5 and later)
Example: Read the value at RTD1
Command: cat /sys/senst2_board/rtd/1
Response: e.i. 100000
Conversion at port of a resistor in Ohm
Formula: Resistance in Ohm = Value / 100
Example: Value = 100000 corresponds 1000Ohm
Conversion at port of a PT1000 temperature sensor to °Celsius
Formula: Temperature in Grad Celsius = (Value / 100 -1000) / 3,891
Example: Value = 112000 corresponds to +30,84°Celsius
Value = 100000 corresponds to 0°Celsius
Value = 90000 corresponds to -25,5°Celsius